Y301-440 4DI+4DO Modbus I/O Module

4DI+4DO I/O Module

Digital Modbus RTU I/O node with four opto-isolated inputs and four SPDT relay outputs for multi-zone control in a compact 115 x 90 x 40 mm enclosure.

  • Modbus-RTU
  • RS485
  • Relay Output
  • Digital I/O
  • DIN Rail

Key Features

01

Four DI + four DO with SPDT relays AC 277 V/10 A or DC 28 V/10 A

02

DI offers wet/dry sensing, pulse counter, and configurable debounce

03

Supports eight linkage rules (follow, timer, pulse, interlock, schedule)

04

DC 5–36V input, DO retention, DIP + software Modbus addressing with watchdog

Specifications

Power Supply

Voltage
DC 5~36V
Typical Current
180 mA @ 12V
Max Current
250 mA (all relays on)
Operating Temperature
-40°C ~ +85°C
Humidity
5% ~ 95% RH, non-condensing

Digital Inputs

Channels
4
Type
Dry/wet contact, opto-isolated
Voltage Range
5~36V (wet contact mode)
Sampling Rate
100 Hz
Pulse Counter
32-bit, selectable rising/falling edge
Debounce
5~255 ms (default 50 ms)

Digital Outputs

Channels
4
Type
SPDT relay
Contact Rating
277 VAC 10 A / 28 VDC 10 A
Minimum Load
10 VAC 10 mA
Electrical Life
100k cycles at rated load
Output Retention
None / soft reboot / full retention

Communication

Interfaces
RS485 (2-wire), optional RS232 or TTL
Protocol
Modbus RTU slave
Baud Rate
600~230400 bps (default 9600)
Slave Address
1~255 (software) + DIP offset 0~31

Mechanical

Dimensions
115 x 90 x 40 mm
Mounting
35 mm DIN clip or screw slots
Protection
IP20